DZ9 Data

 LINE INTERFACES

 E1 ITU-T G.703

 G703.1

 Direct optical link (single mode, nominal wavelength 1310 nm)

 IEEE C37.94

 Analog line interface screw plug connection

 2.048 Mbps, 120 Ohm symmetrical RJ-45 connector or 2 x 75 Ohm asymmetrical BNC connectors
 co-directional 64 kbps, 120 ohm balanced RJ-45 connector

 single mode, nominal wavelength 1310 nm, range up to 100 km, FC/PC connector

 optical connection to digital multiplexers, ST connector

 4-wire duplex transmission, 300 Hz – 3k7 Hz

 COMMANDS

 With digital line interfaces 
 With analog line interface
 Transmission modes:

 Transmission time
          blocking mode:

 up to 8 independent and simultaneous commands 
 up to 4 independent and simultaneous commands 
 blocking
 permissive
 direct
 transparent

 < 3ms (64 kbps)
 < 1ms (2048 kbps)
 < 8 ms (analog line interface)

 INPUTS/OUTPUTS ON COMMAND-SIGNALING UNIT
 Number of command and signaling units CSR
 Inputs/outputs on unit CSR:
          - command inputs
          - programmable command relay outputs
          - utility relay outputs (alarm, signalization)

 1, 2, 3 or 4

  2
  4
  2

 STANDARTS
 RoHS compliant
 МЭК 60834-1
 EN 61000-4-4
 EN 61000-4-5
 EN 55022.B
 EN 60950
CONTROL OF WORK
Software for monitoring and managing Pegasus. Connection via RS232 interface and/or LAN
LEDs on the front panel
Relay contacts
Full access to the remote device via the internal channel
Enabling NMS with SNMP
 POWER SUPPLY
 Power supply
      maximum consumption
 40 – 320 V DC and 82 – 264 V AC
 60 W
 MECHANICAL CONSTRUCTION
  Execution devices
     19” 3HE rack
 Dimensions (W x H x D) weight                     Weight (kg)   
 483 x 170 x 300 mm                                            9